Electrical Safety Management FAQs
Below is a list of all frequently asked questions related to Electrical safety management.
Electrical safety management - Electrical inspection and testing
The purpose of this information sheet is to provide guidance on electrical inspection and testing in accordance with the WHS Regulations 2012 (SA). Please refer to the HSW Handbook Chapter Electrical Safety Management for the overarching responsibilities for electrical safety management.
-
What has changed?
In 2020, SafeWork SA endorsed a revised Code of Practice 鈥淢anaging electrical risks in the workplace鈥. The revised Code has removed an exclusion for the testing of electrical equipment in lower-risk operating environments (such as an office, classroom etc). The testing of such equipment is now required.
-
What electrical equipment do you need to visually inspect?
All electrical equipment in use in the workplace, should be visually inspected by the worker during normal use, to identify obvious damage, wear or other conditions that might make the electrical equipment unsafe.
Visual inspection may identify:
- obvious damage, defects or modifications to the electrical equipment, including accessories, connectors, plugs or cord extension sockets;
- discolouration that may indicate exposure to excessive heat, chemicals or moisture;
- damage to flexible cords/cables;
- damage to operating controls e.g. they are not secured, appropriately identified or broken;
- that covers, guards etc are not secured and not working in the manner intended by the manufacturer or supplier;
- that ventilation inlets and exhausts are obstructed
- the inappropriate use of double adaptors.
-
What can I do if I do not have sufficient power points for the equipment I need?
The use of double adapters is to be discouraged as it is not best practice and is banned in some states. We recommend they be replaced with a power board that has overload protection to protect against fire and electric shocks. Noting that care should be taken not to overload circuits as this will result in tripping out circuits that can potentially lead to delays in work being able to continue whilst waiting for an electrician to be available to reset the circuit.
Where the equipment is likely to remain in that position over the longer term, consideration should be given to a qualified electrician installing additional power points.
-
What equipment do you need to electrically test?
ALL electrical equipment needs to be tested where the equipment is:
- supplied through an electrical socket outlet (i.e. plug in equipment, not hard wired);
- used in an environment in which the normal use of electrical equipment exposes the equipment to operating conditions that are likely to result in damage to the equipment or a reduction in its expected life span (e.g. conditions that involve exposure to moisture, heat, vibration, mechanical damage, corrosive chemicals or dust.);
- a Residual Current Device (RCD).
There are a few exceptions to the above, allowed under the WHS Regulations 2012 (SA) Section 150 and the Code of Practice 鈥淢anaging electrical risks in the workplace鈥.
- New equipment that has never been put into use (other than second-hand equipment). The supplier is deemed responsible for initial electrical safety. Whilst new equipment does not need to be tested, it still needs to be examined for obvious damage and tagged in accordance with AS/NZS 3760 section 2.4.2.1
- Unused electrical equipment that requires testing under the legislation. However, the untested equipment is to be stored in a locked area to prevent use and/or 鈥渓ock out鈥 labels/tags attached.
For equipment that is supplied by cord set, both the cord set and equipment need to be tested and tagged separately.
-
When do you need to test 鈥 at what intervals 鈥 and can I vary this?
Electrical equipment must be inspected and tested at the intervals outlined in the Appendix (Appendix B.2 of the chapter).
The frequency for testing is only able to be varied by a responsible person (deemed as the Head of School/Branch in the Chapter) based on a documented risk assessment undertaken by a competent person. A competent person for the purposes of assessing timeframes for inspecting equipment is a licensed or registered electrician with experience in inspection and testing, including in the application of the AS/NZS 3760.
-
Who can conduct electrical tagging and testing?
Electrical testing and tagging can only be conducted by a competent 鈥淭est & tag鈥 qualified person. A competent person, for the purposes of carrying out inspection and testing of electrical equipment, described in WHS Regulation 150, is a competent person who is licenced or registered to perform electrical work under a law relating to electrical safety or occupational licencing.听 The person should also be competent to interpret the test results of any equipment they use. A person carrying out testing under AS/NZS 3760 could be required to be:
- A licensed or registered electrician (whichever applies); or
- A licensed electrical inspector; or
- A person who has successfully completed a structured training course and been deemed competent in the use of a pass-fail type portable appliance tester and the visual inspection of electrical equipment.
听
The University has a preferred test and tag service provider, eSafe. All external test and tag services will need to be booked through the preferred provider. Refer to听Procurement Services and the 听Information Sheet: Electrical Testing and Tagging using eSafe. Infrastructure will update their procedures to ensure all the requests for testing and tagging are directed to the University鈥檚 preferred supplier.
-
How do I arrange testing of items?
Your local area should already have an annual process in place to test items in accordance with the intervals in the Appendix. If you need to establish a process due to the expanded testing requirements of the Code of Practice , refer to the 听Information Sheet: Electrical Testing and Tagging using eSafe.
-
What about the testing of office equipment, photocopiers and kitchen items?
All electrical equipment must be inspected and tested at the intervals outlined in the Appendix unless a documented risk assessment undertaken by a competent person supports other intervals.
Note that computing equipment that is leased within the testing intervals will not require testing. The supplier is deemed responsible for initial electrical safety and new equipment must be tagged in accordance with AS/NZS 3760 section 2.4.2.1. Centrally purchased equipment through Information Technology and Digital Services, Division of University Operations will be tagged prior to delivery.听
-
Does 成人大片 equipment used at home require testing and tagging?
Electrical equipment owned by the University that is used in the home will need to be tested and tagged.听 However, where the device is connected with a power cord using an AC/DC adapter, thereby ensuring the device is not powered by 240V, only the power cord and adapter need to be brought in for testing and tagging. Where a power cord is plugged directly from the GPO to the device, without an AC/DC adapter, the cord and device must be tested together.
-
What testing is required for hire equipment?
If you are using the electrical equipment hired out you should ensure that, for the period of the hire, the equipment meets all applicable inspection and testing requirements under the WHS Regulations and the Code of Practice 鈥淢anaging electrical risks in the workplace鈥. Responsibility for testing, inspection and tagging passes to the hiree.
-
Does student鈥檚 electrical equipment need testing?
The scope of the Electrical Safety Management chapter including responsibility for tagging and testing applies to:
- all workers who undertake 成人大片 related activities, use 成人大片 facilities and/or are employed or engaged by the University or affiliated with the University in any capacity; and
- the electrical equipment and electrical installations that are under the control of the University.
The University in maintaining its infrastructure, installing RCDs or requiring portable RCDs provides protection for other users of electrical equipment on University premises. Students鈥 electrical equipment, particularly standard equipment such as laptops, mobile phones and chargers would not require testing and tagging under the requirements of this chapter. Students should not be bringing in other items of personal equipment for University purposes.
-
What if my Head of School/Branch wants to test electrical items more frequently?
It is a Head of School/Branch (or delegate) decision. The frequency outlined in the Appendix provide guidance, however additional testing may be conducted if the Head of School/Branch has any safety concerns.
-
What if my Head of School/Branch wants to test electrical items but at a reduced frequency?
If your Head of School/Branch wishes to test less often than the testing frequencies outlined in the Appendix听then you need to seek the advice of a competent person under the WHS Regulations, based on a risk assessment. This advice, including the risk assessment must be kept in accordance with the University鈥檚 records management requirements (Refer to Appendix E of the Chapter Faculty/Division/School/Branch/Area Records). A competent person for the purposes of assessing timeframes for inspecting equipment is a licensed or registered electrician with experience in inspection and testing, including in the application of the AS/NZS 3760.
-
Do I need an electrical plant register?
Requiring a comprehensive report from the supplier of the testing and tagging service should deliver the necessary information for this purpose such as name of person who carried out the testing, equipment description, asset bar code, location, outcome of the test, date of test, next test due date. A record of any testing must be kept in accordance with the University鈥檚 records management requirements (refer to Appendix E of the chapter Faculty/Division/School/Branch/Area Records).
-
What are the requirements for new electrical equipment?
Brand new equipment that has never been put to use (i.e. other than second-hand equipment) does not have to be tested before first use. The supplier is deemed responsible for initial electrical safety. New equipment is to be examined for obvious damage and tagged in accordance with AS/NZS 3760 section 2.4.2.1 (recording the date the electrical equipment was placed into service, the date when the first electrical safety test is due). If equipment requires ongoing testing, then add it to the next testing schedule. Centrally purchased equipment through Information Technology and Digital Services, Division of University Operations will be tagged as above prior to delivery.
Personal equipment needs to be treated as second hand and tested and tagged prior to use in the workplace.
-
I am not sure what the difference is between kinking/coiling/wrapping and crushing/crimping of an electrical cord?
Kinking, coiling and wrapping are words which describes the actions that a person uses when packing up a cord for a laptop computer or a portable projector; it is a folding or coiling action and does not normally result in internal damage to the cord. Crushing and crimping are words which describes when physical damage is likely to occur to the cord e.g. when the cord is stuck in a door, exposed to traffic e.g. car or in a walkway; cut etc.
-
What if a worker brings in personal electrical items from home?
If it is for a one-off event then these items will not require testing, however if your building does not have RCD protection then you will be required to use a portable RCD that has been tested. If it is an item which will remain at work for any period of time, then it will be treated as second hand and therefore is to be tested before it is put into service. Contact Infrastructure Branch for enquiries on RCD protection.
-
What if a student/staff member designs/creates their own electrical equipment?
Any equipment created by a student or staff member must be certified safe by a competent person before being plugged into mains power, electrically inspected and tested before use. All students/staff members are required to be directly supervised by a registered electrical worker.
There are specific legislative requirements for designers of electrical equipment and installations under the WHS Act.
(Electrical equipment includes any apparatus, appliance, cable, conductor, fitting, insulator, material, meter or wire that is used for controlling, generating, supplying, transforming or transmitting electricity at a voltage greater than extra-low voltage.) -
What are the requirements for maintaining electrical testing records?
In accordance with the Code of Practice Managing electrical risks in the workplace, you must ensure that a record of testing carried out on electrical equipment is kept until the electrical equipment is next tested, permanently removed from the workplace, or disposed of. A record of testing must specify the following:
- the name of the person who carried out the test;
- the date of the test;
- the outcome of the test; and
- the date on which the next testing must be carried out.
The record may be in the form of:
- a tag attached to the electrical equipment tested;
- a logbook, database, register or similar kind of record.
Where a tag is used, it must be in accordance with section 2.4.2.1 and be durable, water resistance, non-metallic, self-adhesive or well secured, incapable of re-use and have a bright distinctive surface.
Where a tag is not used you should ensure that tested electrical equipment is marked or labelled so that records of testing can clearly identify the relevant equipment.
-
What is required for testing of residual current devices (RCDs)?
All RCDs used at the workplace are to be tested by a competent person and records of all testing must be kept until the device is next tested or the device is permanently removed from use. This includes all RCDs used in all operating environments including non-portable (fixed) RCDs. If an RCD is tested and found to be faulty it must be taken out of service and replaced as soon as possible.
Testing new portable RCDs
A new portable RCD unit should be tested by pressing the 鈥渢rip test鈥 button to ensure the RCD is effective. -
What is required when inspecting and testing electrical equipment on construction and demolition sites?
The person who is in control of the activity/carrying out the construction work must comply with Further information about construction work can be found in the
-
What is required when inspecting and testing electrical equipment in patient care areas?
specifically excludes medical devices and electrical devices in patient care areas. For more information on these see or .
-
What happens if a visual inspection or electrical testing identifies that the equipment is unsafe?
Where safety concerns are identified they should be reported to Supervisor in control of the area/activity for follow-up. Any unsafe electrical equipment is to be disconnected or isolated from its electricity supply and not reconnected until it is repaired or tested and found to be safe or is replaced or permanently removed from use. The safety concern should be reported using the University鈥檚 to ensure appropriate investigation and corrective action is taken.
-
What if I require further information on electrical testing?
If you require further information, please contact a member of the local HSW Team.
Further information
- The University has a preferred test and tag service provider 鈥 eSafe. Refer to Information Sheet Electrical Testing and Tagging using eSafe
- For any other information, please contact your local HSW Team.